Titulli Shqip
Çelësat për instalimet e palëvizshme elektrike shtëpiake dhe të ngjashme me to -Standard shtesë -Çelësat e zjarrfikëseve për sinjalet dhe ndriçuesit e jashtëm dhe brëndshëm
Titulli Anglisht
Switches for household and similar fixed electrical installations - Collateral standard - Fireman''s switches for exterior and interior signs and luminaires
Scope Shqip
Asnjë informacion i shtuar.
Scope Anglisht
This clause of Part 1 applies with the following modifications: Replacement of the first paragraph: This collateral standard applies to fireman''s switches used for the breaking of the low voltage circuits for exterior and interior signs and luminaires e.g. neon signs for a.c. only with a rated voltage not exceeding 440 V and a rated current not exceeding 125 A. NOTE 1 The working voltage for the signs and luminous-discharge-tube installations is higher than 1 kV but lower than 10 kV and these should be in accordance with EN 50107 series. Renumbering of the subsequent notes. Replacement of the 6th paragraph and the new Note 6 by: Fireman’s switches complying with this standard are suitable for use between –20 °C and +70 °C. NOTE 6 Fireman’s switches are designed for overvoltage category III and used in environment of pollution degree 2 according to EN 60664-1.
Komitetet Teknike
ICS
Direktivë
Asnjë informacion i shtuar.Veprim Kombëtar
SK EN 60669-2-6:2018
replaces
SK EN 50425:2013
- 2016-07-22